Rockwell Automation 1302 575v AC Drive - Canada Only User Manual

Page 66

Advertising
background image

8–8

Programming

Publication 1302-5.0 — January, 1998

FĆ08 RPM at Base Speed

This parameter scales the RPM

display and the setpoint to a

userĆspecified engineering unit.

Parameter Range:

Default Setting:

Step Size:

10 to 9999

1750

1.0 unit

This parameter defines the scaling value applied to the current speed before it is displayed. It is also

used to scale the local reference when FĆ18 is set to ON.

The value to enter into FĆ08 is the maximum value (in RPM, hertz, or any other engineering unit) to be

displayed when the Drive is running at base speed (FĆ07).

Display Scaling Examples

Example 1: Assume that an application requires the display show 1750 RPM when the drive is running

at a base speed of 60 Hz. The RPM display is scaled according to the following equation:

Present Operating Speed (Hz) FĆ08

FĆ07 + Displayed Value

At 30 Hz, the RPM display will show 875:

30 Hz 1750

60 + 875

30 Hz 20

60 + 10

Example 2: Assume the application requires the display show 20 feet per minute for a conveyor (or 20

gallons per minute for a pump) when the motor is running at base speed (FĆ07= 60 Hz). Enter 20 in

parameter FĆ08 to scale the display.
At 30 Hz, the display will show 10 feet (or gallons) per minute: