Rockwell Automation 1302 575v AC Drive - Canada Only User Manual
Page 75
8–17
Programming
Publication 1302-5.0 — January, 1998
FĆ23, FĆ24, and FĆ25 MultiĆSpeed Presets 1, 2, and 3
These parameters allow the
setting of up to three different
preset speeds.
Parameter Range:
Default Setting:
Step Size:
Minimum speed to maximum speed
20 Hz
0.10 Hz
Setting FĆ00 = 3 (multiĆspeed configuration) reconfigures the terminal strip control inputs as follows:
Terminal 6 = START/STOP/IET RESET (open = STOP; closed = IET RESET/START)
Terminal 7 = MSPD 1
Terminal 8 = MSPD 0
Refer to Chapter 5.
Terminals 7 and 8 are used to select the reference source as shown in Table 8.A
Table 8.A - Multi-Speed Presets Digital Inputs
MSPD 1
MSPD 0
Reference Source
Open (0)
Open (0)
Terminal strip analog input (variable speed)
Open (0)
Closed (1)
MultiĆSpeed #1 (FĆ23)
Closed (1)
Open (0)
MultiĆSpeed #2 (FĆ24)
Closed (1)
Closed (1)
MultiĆSpeed #3 (FĆ25)