Rockwell Automation 1302 575v AC Drive - Canada Only User Manual

Page 75

Advertising
background image

8–17

Programming

Publication 1302-5.0 — January, 1998

FĆ23, FĆ24, and FĆ25 MultiĆSpeed Presets 1, 2, and 3

These parameters allow the

setting of up to three different

preset speeds.

Parameter Range:

Default Setting:

Step Size:

Minimum speed to maximum speed

20 Hz

0.10 Hz

Setting FĆ00 = 3 (multiĆspeed configuration) reconfigures the terminal strip control inputs as follows:

Terminal 6 = START/STOP/IET RESET (open = STOP; closed = IET RESET/START)

Terminal 7 = MSPD 1

Terminal 8 = MSPD 0

Refer to Chapter 5.

Terminals 7 and 8 are used to select the reference source as shown in Table 8.A

Table 8.A - Multi-Speed Presets Digital Inputs

MSPD 1

MSPD 0

Reference Source

Open (0)

Open (0)

Terminal strip analog input (variable speed)

Open (0)

Closed (1)

MultiĆSpeed #1 (FĆ23)

Closed (1)

Open (0)

MultiĆSpeed #2 (FĆ24)

Closed (1)

Closed (1)

MultiĆSpeed #3 (FĆ25)

Advertising