8–15

Programming

Publication 1302-5.0 — January, 1998

FĆ20 Password Lockout Enable

This parameter enables or

disables parameter password

protection.

Parameter Range:

Default Setting:

Step Size:

OFF = Password lockout disabled

(parameters can be modified)

ON = Password lockout enabled

(parameters cannot be modified)

OFF

N/A

!

ATTENTION: It is your responsibility to determine how to distribute the password.

Allen-Bradley is not responsible for unauthorized access violations within the user's

organization. Failure to observe this precaution could result in equipment damage or bodily

injury.

When FĆ20 = ON, parameter values can be displayed but cannot be modified (except FĆ20). Entering the

factoryĆset password number (257) toggles the state of the lockout. Refer to Chapter 8, Ensuring Program

Security for this procedure.

Important: There is no visual indication of the status of this feature. You must access FĆ20 to verify its

current value (ON or OFF).

FĆ21 Avoidance Frequency

This parameter specifies the

midpoint of the avoidance band

selected in FĆ22.

Parameter Range:

Default Setting:

Step Size:

Minimum speed to maximum speed (Hz)

5.0

0.10 Hz

The avoidance band can help alleviate problems with vibrations/harmonics at a specific operating

frequency of the driven motor or machinery. Refer to the FĆ22 parameter description for more

information.