5–6
Drive Wiring
Publication 1302-5.0 — January, 1998
Multi–Speed Preset Wiring
Multi-speed preset wiring connects to terminals 6 through 8, and 11.
See Figure 5.7. When control type 3 is selected through parameter
F-00, remote terminal strip control is enabled with multi-speed
presets. This mode of operation changes the functionality of
terminals 6 through 8 and may be used in place of 2- and 3-wire
start/stop wiring. See Figure 5.8.
When you enable multi-speed preset operation, the state of terminals
7 and 8 determine the source of the speed reference:
Terminal 7
Terminal 8
Speed Reference Source
0
0
Terminal Strip Analog Input
0
1
MultiĆSpeed Preset 1 (Parameter FĆ23)
1
0
MultiĆSpeed Preset 2 (Parameter FĆ24)
1
1
MultiĆSpeed Preset 3 (Parameter FĆ25)
Figure 5.7
Multi–Speed Preset Sample Control Wiring
Start/Stop/IET Reset
MultiĆSpeed Preset 2
Fwd
Rev
Function
Loss
Customer
Interlock
MultiĆSpeed Preset 1
Start/Stop/IET Reset
MultiĆSpeed Preset 1
MultiĆSpeed Preset 2
Forward/Reverse
Function Loss
24 VDC Common