Continued ) – Rockwell Automation 1302 575v AC Drive - Canada Only User Manual

Page 88

Advertising
background image

Technical Specifications

A–2

Publication 1302-5.0 — January, 1998

(Continued)

Table A.D - Drive Inputs

Analog Speed Reference 0 to 10ĂVDC or 0 to 20ĂmA
Start

EdgeĆsensitive signal that must see an openĆtoĆclosed contact

transition. This transition may be a momentary or fixed closure.

Stop

An open contact that must be closed when the Drive is running.

The Drive will remain off as long as the contact is open.

IET Reset

EdgeĆsensitive signal that must see an openĆtoĆclosed contact

transition. This transition may be a momentary or fixed closure.

Forward/Reverse

An open contact to assert the forward direction and a closed

contact to assert the reverse direction.

Function Loss

An open contact that must be closed when the Drive is running.

When the contact is open, the Drive turns off. The Drive will remain

off as long as the contact is open.

Table A.E - Drive Outputs

Analog Output
(0Ć10ĂVDC scaled signal)

The scaled signal is selected through parameter FĆ29 and can be

one of the following:

D Output Voltage: 0 to 632 VAC

D % Load (Amps): 0 to 200% (Percentage of output amps

based on the Drive nameplate.)

D RPM/Engineering Unit: Minimum to maximum RPM or

minimum to maximum of any

engineering unit (See parameter

FĆ08)

D % Selected Speed Reference: 0 to 100% (Percentage of

the selected reference

signal range.)

Snubber Resistor Braking Snubber resistor control signal used by an optional snubber

resistor.

Output Status Relay

115 VAC/24 VDC, 0.5 Amp, relay output (One Form A and one

Form B contact wired with a single common.)