Rockwell Automation 1302 575v AC Drive - Canada Only User Manual
Page 77
8–19
Programming
Publication 1302-5.0 — January, 1998
FĆ27 AutoĆRestart Retry Wait Time
This parameter specifies the
amount of timetheDrivewill wait
between autoĆrestart attempts.
Parameter Range:
Default Setting:
Step Size:
1 to 30 seconds
1
1.0 second
This parameter is used with parameter FĆ26 (AutoĆRestart Number of Attempts). Refer to the FĆ26
parameter description for information regarding this feature.
FĆ28 Drive Voltage Selection
This parameter displays the
drive's voltage rating.
Parameter Range:
Default Setting:
Step Size:
N/A
N/A
N/A
!
ATTENTION: This parameter is set at the factory and must not be changed by the user.
Failure to observe this precaution could result in damage to, or destruction of, the equipment.
FĆ29 Analog Output Select
This parameter selects which
monitor modevalueis directed
to the analog output (regardless
of which monitor modevalueis
displayed).
Parameter Range:
Default Setting:
Step Size:
SPd =
Current RPM/speed output
LOAd = Current percent load output
UOL = Current calculated output voltage
rEF =
Current percent of selected
reference
SPd
N/A
Refer to Table A.E in Appendix A for more detail about the analog output.