FĆ27 AutoĆRestart Retry Wait Time

This parameter specifies the

amount of timetheDrivewill wait

between autoĆrestart attempts.

Parameter Range:

Default Setting:

Step Size:

1 to 30 seconds

1

1.0 second

This parameter is used with parameter FĆ26 (AutoĆRestart Number of Attempts). Refer to the FĆ26

parameter description for information regarding this feature.

FĆ28 Drive Voltage Selection

This parameter displays the

drive's voltage rating.

Parameter Range:

Default Setting:

Step Size:

N/A

N/A

N/A

!

ATTENTION: This parameter is set at the factory and must not be changed by the user.

Failure to observe this precaution could result in damage to, or destruction of, the equipment.

FĆ29 Analog Output Select

This parameter selects which

monitor modevalueis directed

to the analog output (regardless

of which monitor modevalueis

displayed).

Parameter Range:

Default Setting:

Step Size:

SPd =

Current RPM/speed output

LOAd = Current percent load output

UOL = Current calculated output voltage

rEF =

Current percent of selected

reference

SPd

N/A

Refer to Table A.E in Appendix A for more detail about the analog output.