FĆ01 Acceleration Time

This parameter specifies the

amount of time it takes the motor

to ramp from stop to the

maximum speed setting in FĆ04.

Parameter Range:

Default Setting:

Step Size:

0.5 to 90 seconds

5.0 seconds

0.10 seconds

If the setpoint frequency requested from the keypad (using the ąą andąą keys) is less than the

maximum speed setting, the time to ramp to that frequency will be proportionally less than the actual

rate setting. For example, if FĆ04 = 60ĂHz and FĆ01 = 4 seconds, it will take 2 seconds to ramp to a

frequency reference of 30 Hz.

Note that if the acceleration rate is set too fast, an overcurrent fault may occur (OC will be displayed).

FĆ02 Deceleration Time

This parameter specifies the

amount of time it takes the motor

to ramp from the maximum

speed setting in FĆ04 to a stop.

Parameter Range:

Default Setting:

Step Size:

0.5 to 90 seconds

5.0 seconds

0.10 seconds

If the frequency requested from the keypad (using the ąą andąą keys) is less than the maximum

speed setting, the time to ramp to that frequency will be proportionally less than the actual rate setting.

For example, if FĆ04 = 60ĂHz and FĆ02 = 4 seconds, it will take 2 seconds to ramp to a frequency

reference of 0ĂHz from 30 Hz.

Note that if the deceleration rate is set too fast, a high bus fault may occur (HU will be displayed).

FĆ03 Minimum Speed

This parameter limits the speed

reference to the Drive.

Regardless of what speed

reference is supplied, the

regulator will not command a

speed less than the value in

FĆ03.

Parameter Range:

Default Setting:

Step Size:

0.5 to 30 Hz

5.0 Hz

0.10 Hz if FĆ04

<

100 Hz

0.25 Hz if FĆ04

100 Hz

!

ATTENTION: The 1302 Drive is intended to operate the motor at a predetermined

minimum speed unless disconnected from the power source. The user is responsible for

assuring safe conditions for operating personnel by providing suitable guards, audible or

visual alarms, or other devices to indicate that the drive is operating at minimum speed,

(possibly zero speed), or the user must verify that the motor output shaft will rotate at all

combinations of load and output speed required by the application.