General Information

Chapter 1

Prepared Space

When ordering a starter kit to complete a prepared space

(2)

, provide the

following information to ensure the proper components are supplied.

Series Number

Provide the series number from the structure with the prepared space. The
number is stamped on a nameplate on the right-hand flange of the starter (see

Figure 1

). The series number is also available from the dimension drawings for

the starter.

Motor Data

Provide the following motor data:

Locked rotor current
Full load current
Maximum locked rotor time
Acceleration time
Motor service factor
Motor horsepower

Starter Features

Provide information regarding any special features required for the starter kit.
Indicate if these features are different from the motor control features in the
existing, complete power cell.

Recommended Torque
Values

When reinstalling components or when reassembling the cabinet, tighten the
following bolt sizes to the specified torque values:

Table 1 - Hardware Torque Values

(2) Not available on arc resistant cabinets.

1/4 in. hardware

8 N•m (6 lb•ft)

5/16 in. hardware

15 N•m (12 lb•ft)

3/8 in. hardware

27 N•m (20 lb•ft)

1/2 in. hardware

65 N•m (48 lb•ft)

Advertising