Additional notes, Plenum exhaust considerations, Figure 73 – Rockwell Automation 1512B MV Controllers, 200/400A Two-High Cabinet, Standard and Arc-Resistant Enclosure User Manual

Page 83

Advertising
background image

Rockwell Automation Publication 1500-UM055G-EN-P - May 2013

75

ArcShield Unit Information

Appendix A

Figure 73 - Chimney Exhaust Space Requirements

Minimum H1: 1.7 m (67 inches)
Minimum H: 1 m (39 inches)

Additional Notes

The walls of the plenum exit area must be capable of withstanding the

pressure generated.

Any painted surfaces which face direct contact with the arc products may

ignite. Flame suppression is recommended.

The exit point can also be outside the building. Ensure exit area can not be

blocked by ice, snow, or vermin nests.

Access barriers are recommended as a means of restricting access by

personnel while the equipment is energized. Chain link fencing is a
suitable barrier material.

Equipment that consists of more than 4 vertical sections bolted together

may require additional plenum exits. Rockwell Automation will provide
guidance on requirements for additional plenum exits when required.