Auxiliary contacts inspection and replacement – Rockwell Automation 1512B MV Controllers, 200/400A Two-High Cabinet, Standard and Arc-Resistant Enclosure User Manual

Page 71

Advertising
background image

Rockwell Automation Publication 1500-UM055G-EN-P - May 2013

63

Maintenance

Chapter 5

3. To adjust the distance from the blades to the bar, disconnect the threaded

connecting rod at the handle operating lever (see

Figure 57

).

4. Turn the threaded connecting rod to lengthen or shorten it. This will

adjust the position of the isolation switch blades in the ON and OFF
position.

Auxiliary Contacts Inspection
and Replacement

1. Complete the Power Lock-out Procedure (refer to

Power Lock-out

Procedure on page 47

).

2. Inspect the auxiliary contacts for wear, scorching or heat damage. Replace

any damaged contacts. The contacts have a mean time between failure
(MTBF) rating of 20 million operations if used within the operating
specifications.

3. To remove the contact, turn both of the D-head fasteners until the flat

sections are aligned with the edge of the contact (see

Figure 64

).

4. Remove the contact from the housing.

5. Disconnect the wires from the auxiliary contact.

6. Reverse the procedure to replace the auxiliary contact.

7. Ensure the contact is correctly positioned into the contact carrier (see

Figure 64

).

Figure 64 - Auxiliary Contact Orientation

ATTENTION: To avoid shock hazard, lock out incoming power (refer to

Power

Lock-out Procedure on page 47

) before working on the equipment. Verify with a

hot stick or appropriate voltage measuring device that all circuits are voltage
free. Failure to do so may result in severe burns, injury or death.

CATALOG NO.

700-CPM

SER. A

20

AMP

CATA

LOG NO.

700-CPM

SER. A

20

AMP

CATALOG NO.

700-CPM

SER. A

20

AMP

CATALOG NO.

700-CPM

SER. A

20

AMP

CATA

LOG NO.

700-CPM

SER. A

20

AMP

CATA

LOG NO.

700-CPM

SER. A

20

AMP

D-head Fastener

Correct

Incorrect