8. Actuate the Isolation Switch handle to verify the travel angle.

If the angle is incorrect, repeat steps 5 through 7 until desired travel angle is
reached.

Isolation Switch Mechanism
Grounding Adjustment

1. Complete the Power Lock-out Procedure (refer to

Power Lock-out

Procedure on page 47

).

2. Inspect the grounding of the isolation switch blades. When the isolation

switch handle is in the OFF position, the isolation switch blades must fully
engage the grounding pins and be within 1.5 mm (0.06 in.) of the ground
bar (see

Figure 63

). When the isolation switch handle is in the ON

position, the blades must fully engage the incoming line stabs.

Figure 63 - Isolation Switch Grounding Adjustment

ATTENTION: All three isolation switch linkage assemblies must meet the angle
tolerance requirements.

ATTENTION: To avoid shock hazards, lock out incoming power (refer to

Power

Lock-out Procedure on page 47

) before working on the equipment. Verify with a

hot stick or other appropriate voltage measuring device that all circuits are
voltage free. Failure to do so may result in severe burns, injury or death.

Ground Bar

Maximum Gap 0.06 in. (1.5 mm) between ground
Bar and Isolation Switch in open position

Isolation Switch Blade

Incoming Line Stab

Auxiliary Contact