Figure 57 - Isolation Switch Handle Mechanism Lubrication Points

5. Inspect the mounting hardware on the isolation switch operating lever and

contactor interlock rod (see

Figure 57

). Tighten any loose hardware.

6. Inspect the isolation switch blades and the incoming line stabs (see

Figure 63

). The mating surfaces must be clean and well lubricated.

7. Remove any dirt and dried grease.

8. Lubricate the isolation switch blades and the isolation switch blade pivot

points with Nyogel 759G (see

Figure 58

).

Contactor Interlock Rod

Lubrication Points

(at replacement only)

Interlock Lever

Clevis Pins and Cotter Pins

Threaded Connecting Rod

Isolation Switch
Operating Lever

IMPORTANT

Do not scrape or file the parts. This may remove the plating and expose
the underlying copper to corrosion.

IMPORTANT

Lubricate the isolation switch blades a minimum of once per year to
avoid excessive wear to the components and to prevent the isolation
switch blades from overheating.