Rockwell Automation Publication 1500-UM055G-EN-P - May 2013

23

Installation – Arc-Resistant Enclosure (ArcShield)

Chapter 3

6. Reverse the procedure to close the door. Door lock bolts must be

adequately tightened (refer to

Recommended Torque Values on page 3 of

Chapter 1

for torque values).

Figure 22 - Label on Arc Resistant Door

Anchoring

Place the controller in the desired installation location. Use 12 mm (1/2 in.
[M12]) floor mounting bolts to securely fasten the controller to the mounting
surface. See

Figure 23

as an example of the location of the mounting holes in the

cabinet.

IMPORTANT

When closing the medium voltage door, ensure all door locking bolts
on the right side of the MV door are in place and tightened until the
door is flush with the flange. Do not overtighten the bolts. If the
door is not securely fastened, it will not be possible to move the
isolation switch handle to the ON position.

TIP

On all ArcShield starters, the sticker in

Figure 22

is attached to each

door for your reference.

TIP

Refer to Dimension Drawing provided with order documentation for additional
details related to cabinet floor plan.