Joining sections – Rockwell Automation 1512B MV Controllers, 200/400A Two-High Cabinet, Standard and Arc-Resistant Enclosure User Manual

Page 33

Advertising
background image

Rockwell Automation Publication 1500-UM055G-EN-P - May 2013

25

Installation – Arc-Resistant Enclosure (ArcShield)

Chapter 3

Joining Sections

1. Position the left side section on a level surface and secure the section in

place with 12 mm (1/2 in. [M12]) floor mounting bolts (refer
to

Anchoring on page 23

).

2. When joining ArcShield sections, apply a continuous 3 mm (1/8 in.) wide

bead of silicone sealer around the perimeter of one section.

3. Remove the side bus access covers if applicable.

4. Position the right section against the left section. Ensure that the surface is

level.

5. Secure the sections together using the 1/4-20 self-tapping screws. Thread

the screw through the 7 mm (0.281 in.) clearance hole to the
corresponding 6 mm (0.219 in.) pilot hole. To access the front clearance
holes of the left-side cabinet, open the medium voltage doors. To access the
rear clearance holes remove the rear covers of the starter. If rear access is
not available, refer to

Front Access– Access to Power Bus on page 11 of

Chapter 2

. When joining the ArcShield sections, use the provided 1/4-20

thread fasteners to secure the perimeter of the horizontal bus opening,
ensure all bolts are installed. (Before joining sections together, ensure there
is a silicone seal around the bus bar opening.)

6. Secure the right section to the floor using 12 mm (1/2 in. [M12]) floor

mounting bolts (refer to

Anchoring on page 23

).

Figure 24 - Joining Sections

TIP

Joining hardware can be found in a package mounted to the front of the
shipping skid.

TIP

Refer to publication MV-QS050_-EN-P for level floor surface requirements.

Power Bus

cutout holes

must align

Silicone is applied around

power bus cutout area to

prevent gas leakage

between joined cabinets