Rockwell Automation Publication 1500-UM055G-EN-P - May 2013

Chapter 3

Installation – Arc-Resistant Enclosure (ArcShield)

6. If access to the right side of the power bus is required, remove the vacuum

contactor from the upper power cell (refer to

Removing the Contactor on

page 52 of Chapter 5

).

7. Remove the power fuses from the isolation switch.

8. Remove the interphase barriers from the trailer fuse block by raising them

vertically up and out of the mounting slots (see

Figure 32

).

9. Use a 9/16-in. socket to remove the contactor bus bars from the isolation

switch trainer fuse block.

Figure 32 - Contactor Bus Bars (Trailer Fuse Block for Clip-on Fuses Shown)

10. Disconnect the secondary control wiring from the control power

transformer (CPT) and remove the CPT mounting plate. Leave the CPT
attached to the plate.

11. To access the right side of the power bus, remove the self-tapping screws

from the lower glass-polyester bus access cover and remove the cover (see

Figure 33

).

12. Reverse the procedure to reassemble the cabinet. Ensure that the barriers

are put back in place.

Contactor Bus Bars

Mounting Bolts

Trailer Fuse Block

ATTENTION: The CPT is heavy and assistance may be required to safely
remove and transport the unit. Use caution when removing the CPT.
Failure to do so may result in personal injury and/or damage to the
equipment.