Rockwell Automation Publication 1500-UM055G-EN-P - May 2013

73

ArcShield Unit Information

Appendix A

Figure 70 - Cross-section of Plenum Extension, dimensions in inches [mm]

Plenum Exhaust Considerations

The following options for locating the plenum exhaust are presented:

1. Plenum ducted to an area of the control room where arc gases are permitted

to escape, with plenum extensions (see

Figure 71

,

Figure 72

and

Figure 73

).

2. Plenum duct to outside of control room (see

Figure 71

and

Figure 72

).

Plan the location where the plenum will exhaust. Ensure that:

There is no access to personnel while equipment is energized.

Area is free of flammable material or vapors

Ensure that adequate space is provided around the plenum exhaust, as outlined in

Figure 71

through

Figure 73

.

23 [584]

25 [633]

IMPORTANT

Be aware that equipment in the area of the plenum exhaust point will be
damaged or destroyed.