Figure 71, Figure 72 – Rockwell Automation 1512B MV Controllers, 200/400A Two-High Cabinet, Standard and Arc-Resistant Enclosure User Manual

Page 82

Advertising
background image

74

Rockwell Automation Publication 1500-UM055G-EN-P - May 2013

Appendix A

ArcShield Unit Information

Figure 71 - Plenum Exit Left with Extensions to Internal Controlled Access Area (Top View)

Figure 72 - Plenum Exit Left with Extension(s) to Internal Controlled Access Area (Front View)

Minimum H = 3.5 m (138 inches)
Minimum L = 1.2 m (47 inches)
Minimum Volume of space required for safe pressure relief: X * Y * H = 11 m

3

(390 cubic feet)

X

L

Y

Personnel
Access Barrier

H

L

Personnel

Access Barrier