Rockwell Automation Publication 1500-UM055G-EN-P - May 2013

77

Appendix

B

ArcShield Plenum Installation Instructions

The following instructions are provided to ensure the proper installation and
function of plenum components supplied with ArcShield enclosures. Refer to

Appendix A

for additional information related to ArcShield plenums before

attempting to follow these instructions.

Recommended Torque
Values

1/4-20 Thread Fasteners – 7.5 N•m (6 lb•ft)
5/16-18 Thread Fasteners – 14 N•m (11 lb•ft)

Plenum Bracing

Bracing of the plenum must be able to withstand the dynamic forces of the arc
fault as well as any other vibration or seismic effects associated with the
installation. Most of this force will be in the direction opposite to where the relief
vent exits. The amount of bracing will depend on how the plenum is supported at
its exit as well as the distance from the end of the cabinets to the exit vent.

A flange is available for installing hangers to support the plenum weight.
The plenum extension has holes for mechanical support.
Weight per unit length of Rockwell supplied plenum = 28 kg/m (19 lb/ft).
Installer is responsible for ensuring that the plenum extension has

sufficient support to resist the effect of vibrations and seismic effects.

Figure 74 - Plenum Exhaust Label

IMPORTANT

Plan the location where the plenum will exhaust (refer to

Appendix A

).

Equipment in the area of the plenum exhaust will be damaged or destroyed.
Mark the plenum exhaust area as a Hazardous Zone (

Figure 74

).

ARC FLASH HAZARD

PRESSURE RELIEF EXIT

AREAS TO BE:

- INACCESSIBLE TO PERSONNEL
WHILE EQUIPMENT ENERGIZED.
- FREE OF OBSTRUCTIONS
(REFER TO USER MANUAL).

SEVERE INJURY OR

DEATH MAY RESULT.

SORTIE DE L’ÉVENT

RÉGION ÊTRE:

- INACCESSIBLE AUX PERSONNEL
PENDANT QUE L’ÉQUIPEMENT
EST SOUS TENSION.
- DÉMUNI D’OBSTRUCTIONS
(RÉFÉRER AU MANUEL)

RISQUE DE BLESSURES

CORPORELLES GRAVES

OU MÊME LA MORT.

DANGER

DANGER

HAZARD D’ARC ÉLECTRIQUE