Rockwell Automation Publication 1500-UM055G-EN-P - May 2013

Chapter 5

Maintenance

10. Move the stop bracket until it just touches the interlock lever and tighten

the screws.

11. Apply Loctite 290 (or equivalent adhesive) to the stop bracket screws and

torque the screws to 8 N•m (6 lb•ft).

12. Move the isolation switch handle to the ON position.

13. Manually close the contactor by attaching locking pliers to the contactor

interlock lever and pushing down until the armature plate contacts the
magnetic cores (see

Figure 55

). Verify that the interlock lever overlaps the

isolation switch operating lever by at least 3 mm (0.125 in.) (see

Figure 56

).

Figure 55 - Closing Contactor Manually (Some parts not shown)

Contactor
Interlock Rod

Contactor Plug

Contactor

Mounting Bolts

Contactor

Operating Lever