Rockwell Automation Publication 1500-UM055G-EN-P - May 2013

17

Installation – Standard Enclosure

Chapter 2

Figure 16 - Bottom Cable Exit Configuration

Load Cable Connections

1. Complete the Power Lock-out procedure (refer to

Power Lock-out

Procedure on page 47 of Chapter 5

).

2. Open the MV power cell door.

3. Remove the cable duct boot at the top of the cabinet for top exiting load

cables, or remove the one at the bottom of the cabinet for bottom exiting
load cables (see

Figure 17

).

Cable Duct Barrier

Cable Duct Boot

ATTENTION: To avoid shock hazards, lock out incoming power (refer to

Power

Lock-out Procedure on page 47 of Chapter 5

) before working on the equipment.

Verify with a hot stick or appropriate voltage measuring device that all circuits
are voltage free. Failure to do so may result in severe burns, injury or death.

IMPORTANT

The current transformers may be positioned for top or bottom cable exit.
Follow the appropriate procedure described for your starter configuration.

IMPORTANT

Refer to Dimensional Drawings provided with order documentation for
additional details.