Chapter 2 Powermonitor 1000 Memory Organization

The power monitor requires a valid password before it accepts a
write. There are two ways a password may be written.

An entire table including a valid password may be written.

A valid password may be written to the Single element password
write table which then enables single element writes until
30 minutes without a single element write elapses.

Data Table Data Format

The power monitor stores data in two basic formats.

Integer, in which the 16-bit word may be represented by a
signed integer value or a bit field

Floating-point, in the 32-bit IEEE 754 format

Modbus input registers and holding registers are 16 bits long. Floating
point values in the data tables are represented as big-Endian
two-register arrays in IEEE-754 floating point format. The Modbus
client application must be able to reassemble the two-word array into
a valid floating-point value.

An example Modbus address for a floating-point value is 40101-2.
Register 40101 holds the most significant bytes of the number and
40102 holds the lowest significant bytes.