Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 66

Advertising
background image

66

Publication 1408-UM001B-EN-P - May 2008

Appendix A Powermonitor 1000 Data Tables

Controller Interface Table Parameters

CSP File No.

N18

CIP Instance

11

Applies to

EM2, EM3 only

No. of Elements

8

No. of Words

8

Data Type

Integer

Data Access

Write

Controller Interface Table

Element
No.

Modbus
Address

Element Name Default

Value

Range

Description

0

40801

Password

0

0…9999

When writing the complete table this parameter allows the input
data to be accepted. When writing a single parameter the separate
password table should be used. Returns -1 on a read.

1

40802

Controller
Command Word

0

0…1

Bit 0 = When this bit is written to the power monitor it signals the
end of the demand period. The power monitor resets the bit to 0 and
sends the end of demand broadcast to all of the slaves configured for
the master/slave demand system. The power monitor must be
configured as a Master for external demand pulse input.
Bit 1…15 = Reserved

2

40803

Reserved

0

0

Reserved for future use.

3

40804

Reserved

0

0

Reserved for future use.

4

40805

Reserved

0

0

Reserved for future use.

5

40806

Reserved

0

0

Reserved for future use.

6

40807

Reserved

0

0

Reserved for future use.

7

40808

Reserved

0

0

Reserved for future use.