Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 71

Advertising
background image

Publication 1408-UM001B-EN-P - May 2008

71

Powermonitor 1000 Data Tables Appendix A

6

30213-14

L3-N Volts

0.000…9,999,999

Phase 3 scaled RMS Voltage

7

30215-16

Average L-N Volts

0.000…9,999,999

Averaged RMS Voltage

8

30217-18

L1-L2 Volts

0.000…9,999,999

Line 1 to Line 2 Volts

9

30219-20

L2-L3 Volts

0.000…9,999,999

Line 2 to Line 3 Volts

10

30221-22

L3-L1 Volts

0.000…9,999,999

Line 3 to Line 1 Volts

11

30223-24

Average L-L Volts

0.000…9,999,999

Average Line to Line Volts

12

30225-26

Frequency

40.0 Hz…70.0 Hz

Last frequency reading.

13

30227-28

Percent Current
Unbalance

0.0…100.0

Percent maximum deviation from
Ave. / Ave.

14

30229-30

Percent Voltage
Unbalance

0.0…100.0

Percent Maximum deviation from
Ave. / Ave.

15

30231-32

Metering Iteration

0…9,999,999

Increments by 1 for each new
metering calculation.

Volts, Amps, Frequency Results

Element
No.

Modbus
Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

Power Results Parameters

CSP File No.

F22

CIP Instance

15

No. of Elements

17

No. of Words

34

Data Type

Float

Data Access

Read

Power Results

Element
No.

Modbus
Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

0

30301-2

L1 True Power
Factor

-100.0…+100.0

Percent ratio between power and
apparent power. The value is
signed to (+) leading and (-)
lagging.

1

30303-4

L2 True Power
Factor

-100.0…+100.0

2

30305-6

L3 True Power
Factor

-100.0…+100.0

3

30307-8

3 Phase True
Power Factor

-100.0…+100.0

4

30309-10

L1 kWatts

+/- 0.000…9,999,999

Line 1 kWatts

5

30311-12

L2 kWatts

+/- 0.000…9,999,999

Line 2 kWatts

Advertising
This manual is related to the following products: