Powermonitor 1000 Data Tables Appendix A

11

40123-24

KYZ Pulse
Duration
Setting

250 ms

0 or
50…1000

Set as 50…1000 to indicate the duration
of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
The value for delay is rounded off to the
nearest 10ms internally during this
function.

12

40125-26

Status Input
1 Input Scale

1

1…
1,000,000

When a status pulse is received the count
is increased by the scale factor. Input
pulse * input scale added to total status
count.

13

40127-28

Status Input
2 Input Scale

1

1…
1,000,000

When a status pulse is received the count
is increased by the scale factor. Input
pulse * input scale added to total status
count.

14

40129-30

Demand
Source

0

0…3

When item Demand Broadcast Master
Select of the ethernet table is set to
master a selection of 0 through 2 sets the
type of master input. In this case item 3 is
ignored. When the Demand Broadcast
Master Select of the ethernet table is set
to slave then any of these inputs can set
the end of the demand period. Selections
of 0 through 2 can be selected for RS485
units.

0 = Internal Timer
1 = Status Input 2
2 = Controller Command
3 = Ethernet Demand Broadcast

Selection 3 can only be programmed when
the Ethernet option is installed.

15

40131-32

Demand
Period
Length

15 min

0…99

Specifies the desired period for demand
calculations. When set to 0 there are no
projected demand calculations. If the
internal timer is selected a setting of 0
turns the demand function off.

16

40133-34

Number of
Demand
Periods

1

1…15

Specifies the number of demand periods
to average for demand measurement.

Advanced Configuration

Element
No.

Modbus
Address
Range

Element
Name

Default
Value

Range

TR1

TR2

EM1

EM2

EM3

Description