6

31113-14

Peak Demand
kVAR

+/- 0.000…
9,999,999

The largest magnitude demand for
kVAR that occurred over all of the
demand intervals since the last clear
command or auto-clear day.

7

31115-16

Average Demand
kVAR

+/- 0.000…
9,999,999

A running average of demand for kVAR
from the end of each demand period
since the last clear command or
auto-clear day.

8

31117-18

Load Factor kVAR

0…100%

Average Demand kVAR / Peak Demand
kVAR. This is a demand management
metric that indicates how ‘spiky’ (or
‘level’) a load is over a period of time
(usually 1 month). A value approaching
100% indicates a constant load.

9

31119-20

Peak Demand kVA

0.000…
9,999,999

The largest magnitude demand for kVA
that occurred over all of the demand
intervals since the last clear command
or auto-clear day.

10

31121-22

Average Demand
kVA

0.000…
9,999,999

A running average of demand for kVA
from the end of each demand period
since the last clear command or
auto-clear day.

11

31123-24

Load Factor kVA

0…100%

Average Demand kVA / Peak Demand
kVA. This is a demand management
metric that indicates how ‘spiky’ (or
‘level’) a load is over a period of time
(usually 1 month). A value approaching
100% indicates a constant load.

12

31125-26

Reserved

0

Reserved for Future Use

13

31127-28

Reserved

0

Reserved for Future Use

Load Factor Log Results

Element
No.

Modbus
Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description