Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 83

Advertising
background image

Publication 1408-UM001B-EN-P - May 2008

83

Powermonitor 1000 Data Tables Appendix A

Min/Max Log Results Parameters

CSP File No.

F29

CIP Instance

22

No. of Elements

11

No. of Words

22

Data Type

Float

Data Access

Read

Min/Max Log Results

Element
No.

Modbus
Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

0

31001-2

Parameter Being
Returned

1…35

Indicates the Parameter Number (See
Min/Max Parameter List).

1

31003-4

MIN Value

+/-
0.000…9,999
,999

The minimum value recorded for
parameter being returned since the
last clear command.

2

31005-6

MAX Value

+/-
0.000…9,999
,999

The maximum value recorded for
parameter being returned since the
last clear command.

3

31007-8

Timestamp Year of
MIN

The year when the MIN value was
recorded.

4

31009-10

Timestamp
Month/Day of MIN

The month and day when the MIN
value was recorded.

5

31011-12

Timestamp
Hour/Minute of MIN

The hour and minute when the MIN
value was recorded.

6

31013-14

Timestamp Seconds/
Hundredths of MIN

The seconds and hundredths when the
MIN value was recorded.

7

31015-16

Timestamp Year of
MAX

The year when the MAX value was
recorded.

8

31017-18

Timestamp
Month/Day of MAX

The month and day when the MAX
value was recorded.

9

31019-20

Timestamp
Hour/Minute of MAX

The hour and minute when the MAX
value was recorded.

10

31021-22

Timestamp Seconds/
Hundredths of MAX

The seconds and hundredths when the
MAX value was recorded.

Advertising