Publication 1408-UM001B-EN-P - May 2008

19

Explicit Messaging Chapter 4

Follow these steps to configure a message.

1. Choose the appropriate parameters in the Message

Configuration window.

2. Click the Communication tab to select the communication type,

either Ethernet or Serial.

Parameter

Choice

Message type

Select the appropriate message type according to

Message Type

on

page 18

.

Source Element

Read: Refer to

Appendix A

– Powermonitor 1000 Data Tables for the

address of the specific data table address you’re reading. If you are
performing a multiple element read, this should be the first element in
the array of elements you’re reading back.

Write: This is the controller tag in which to store the data being
written to the power monitor.

Number of
Elements

This is the number of elements being read or written to. If you are
performing a single element read or write, then this value should be 1.
If you are performing a multiple element read or write, then this should
be the number of elements after the source element that you wish to
read or write.

Destination
Element

Read: This is the controller tag in which to store the data being read.

Write: Refer to

Appendix A

– Powermonitor 1000 Data Tables for the

address of the specific data table address you’re writing to.