Explicit Messaging Chapter 4

RSLogix500 Software - Message Setup Using PLC5 or SLC Typed
Read/Write

The following is an example of how to set up your message
instruction to read or write single or multiple elements to a power
monitor using Peer-To-Peer PLC5 or CPU 500 Typed messages in
RSLogix500 software. This setup applies to SLC and MicroLogix
programmable logic controllers.

Follow these steps to configure a message.

1. Set your MSG instruction.

2. Click Setup Screen at the bottom of the message instruction.

The message configuration window for either Ethernet network
or Serial communication appears.

Parameter

Choice

Read/Write

Select Read or Write

Target Device

Select the appropriate message type according to

Message Type

on

page 18

.

Local/Remote

Select Local

Control Block

Select an available Integer word. In this example, we used N7:0.