Appendix A Powermonitor 1000 Data Tables

Unit Run Status Results Parameters

CSP File No.

N28

CIP Instance

21

Applies to

All models

No. of Elements

25

No. of Words

25

Data Type

Integer

Data Access

Read

Unit Run Status Results

Element
No.

Modbus
Address

Element Name

Range

Description

0

30901

Bulletin Number

1408

Always returns 1408

1

30902

Series Letter

0…8

Indicates the unit hardware series letter, for
example.
0 = A
1 = B
.
.
8 = H

2

30903

Catalog Device Type

0…4

The catalog number type of this device.
0 = TR1
1 = TR2
2 = EM1
3 = EM2
4 = EM3

3

30904

Communication Type

0…1

The communication type of this device
0 = Serial only
1 = both serial and Ethernet

4

30905

Application FRN

-

The current firmware revision

5

30906

Boot Code FRN

-

The current boot code revision

6

30907

Default Device ID

1…247

A semi-unique number assigned to a device at the
time it is manufactured. Used for out of the box
communications over DF1 and Ethernet.

7

30908

Accuracy Class

0…3

Indicates the revenue metering accuracy class of
the power monitor as it is shipped from the
factory.
0 = No Class Designation
1 = Class 1
2 = Class 0.5
3 = Class 0.2

Advertising
This manual is related to the following products: