Powermonitor 1000 Data Tables Appendix A

8

30909

Overall Status

0…16383

0 indicates normal operation. Each bit indicates a
different fault condition.
Bit 0 = Flash Memory
Bit 1 = SRAM
Bit 2 = NVRAM
Bit 3 = SPI Interface
Bit 4 = Real Time Clock
Bit 5 = Watchdog Timer
Bit 6 = Metering
Bit 7 = LCD Interface
Bit 8 = Serial Communications
Bit 9 = Ethernet Communications
Bit 10 = Error Log Full

9

30910

Flash Memory

0…511

0 indicates normal operation. Status bits are
Bit 0 = Overall status
Bit 1 = Boot code checksum
Bit 2 = Application code checksum
Bit 3 = Calibration data CRC
Bit 4 = No calibration data
Bit 5 = Wrong application FRN
Bit 6 = Invalid model type
Bit 7 = WIN mismatch
Bit 8 = missing upgrade block

10

30911

SRAM

0…1

0 indicates normal operation.
Bit 0 = Read/write test

11

30912

NVRAM

0…1

0 indicates normal operation.
Bit 0 = Read/write test

12

30913

SPI Interface

0…1

0 indicates normal operation.
Bit 0 = SPI device not responding

13

30914

Real Time Clock

0…3

0 indicates normal operation.
Bit 0 = RTC status
Bit 1 = Time Zone Set Failed

14

30915

Watchdog Timer

0…1

0 indicates normal operation.
Bit 0 = Watchdog time out

15

30916

Metering

0…1

0 indicates normal operation.
Bit 0 = Metering status

16

30917

LCD Interface

0…1

0 indicates normal operation.
Bit 0 = LCD Interface status

17

30918

Serial Communications

0…1

0 indicates normal operation.
Bit 0 = Serial Interface status

Unit Run Status Results

Element
No.

Modbus
Address

Element Name

Range

Description