Appendix A Powermonitor 1000 Data Tables

User Configurable Table Setup Parameters

CSP File No.

N36

CIP Instance

29

Applies to

EM3 only

No. of Elements

17

No. of Words

17

Data Type

Integer

Data Access

Read/Write

User Configured Table Setup

Element
No.

Modbus
Address

Element Name

Default Value

Range

Description

0

41001

Password

0

0…9999

Required for configuration,
returns -1.

1

41002

Selection for Parameter #1

29 (L1 Current)

0…110

2

41003

Selection for Parameter #2

30 (L2 Current)

3

41004

Selection for Parameter #3

31 (L3 Current)

4

41005

Selection for Parameter #4

37 (L1-L2 Voltage)

5

41006

Selection for Parameter #5

38 (L2-L3 Voltage)

6

41007

Selection for Parameter #6

39 (L3-L1 Voltage)

7

41008

Selection for Parameter #7

41 (Frequency)

8

41009

Selection for Parameter #8

52 (Total Real Power)

9

41010

Selection for Parameter #9

56 (Total Reactive Power)

10

41011

Selection for Parameter #10

60 (Total Apparent Power)

11

41012

Selection for Parameter #11

48 (3 Phase True Power Factor)

12

41013

Selection for Parameter #12

70 (Real Energy Net (kWh))

13

41014

Selection for Parameter #13

62 (Status 1 Count x1)

14

41015

Selection for Parameter #14

64 (Status 2 Count x1)

15

41016

Selection for Parameter #15

79 (Real Power Demand)

16

41017

Selection for Parameter #16

8 (Status Input States)