SCADA Applications Chapter 5

Reading the User Configured Table as Connected Instance 1

The following example illustrates the steps required to set up an I/O
connection between a Logix controller and the user configured
Instance 1. The example uses a CompactLogix controller and
RSLogix 5000 software.

Follow these steps to configure the connection.

1. Open an offline project in RSLogix 5000 software.

2. Open the Ethernet network interface and select the Ethernet

network.

3. Add a new module and choose Generic Ethernet Module from

the Communications group.

4. Configure the properties of the new module and click OK.

Parameter

Choice

Name

Your choice of name

Comm Format

Input Data - REAL

IP Address

The IP address of your power monitor

Input

Assembly Instance 1; Size 16 (32-bit)

Output

Assembly Instance 2

Configuration

Assembly Instance 3; Size 0

Open Module Properties

Leave checked