Powermonitor 1000 Data Tables Appendix A

4

40505

Off Peak Days

65

0…127

This bit map field selects the off peak
days. OFF-PEAK days have only one rate
for billing.

Bit0= Sunday
Bit1= Monday
Bit2= Tuesday
Bit3= Wednesday
Bit4= Thursday
Bit5= Friday
Bit6= Saturday
Saturday and Sunday are default Off
Peak days.

5

40506

MID Peak AM
Hours

1792

0…
4095

This bit map selects any AM hours that
are designated as MID Peak. Example:
The hours from 8 AM to 11AM is
designated as bit 8 through bit 10 =
1792d.

Bit0= 12 AM…1 AM
Bit1= 1 AM…2 AM
Bit2= 2 AM…3 AM


Bit11= 11AM…12 AM
Default is 8 AM…11 AM

6

40507

MID Peak PM
Hours

120

0…
4095

This bit map selects any PM hours that
are designated as MID Peak. Example:
The hours from 3 PM to 7 PM is
designated as bit 3 through bit 6 = 120d.

Bit0= 12 PM…1 PM
Bit1= 1 PM…2 PM
Bit2= 2 PM…3 PM


Bit11= 11PM…12 PM
Default is 3 PM…7 PM

7

40508

ON Peak AM
Hours

2048

0…
4095

This bit map selects any AM hours that
are designated as ON Peak. Example:
The hours from 11AM to 12 PM is
designated as bit 11 = 2048d.

Bit0= 12 AM…1 AM
Bit1= 1 AM…2 AM
Bit2= 2 AM…3 AM

Bit11= 11AM…12 AM
Default is 11AM

Log Configuration

Element
No.

Modbus
Address

Element Name Default

Value

Range

TR1

TR2

EM1

EM2

EM3

Description