Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 78

Advertising
background image

78

Publication 1408-UM001B-EN-P - May 2008

Appendix A Powermonitor 1000 Data Tables

Energy Log Results Parameters

CSP File No.

F26

CIP Instance

19

No. of Elements

21

No. of Words

42

Data Type

Float

Data Access

Read

Energy Log Results

Element
No.

Modbus
Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

0

30701-2

Internal Record
Identifier.

1

30703-4

Timestamp Year of
record

-

The date and time when the
record was recorded.

2

30705-6

Timestamp
Month/Day

-

3

30707-8

Timestamp
Hour/Minute

-

4

30709-10

Timestamp
Seconds/

Hundredths

-

5

30711-12

Status 1 Count xM

0…9,999,999

Status 1 Count times
1,000,000

6

30713-14

Status 1 Count x1

0…999,999

Status 1 count times 1

7

30715-16

Status 2 Count xM

0…9,999,999

Status 2 Count times
1,000,000

8

30717-18

Status 2 Count x1

0…999,999

Status 2 count times 1

9

30719-20

GWh Net

+/- 0…9,999,999

Net gigawatt hours

10

30721-22

kWatth Net

+/- 0.000…999,999

Net kilowatt hours

11

30723-24

GVARH Net

+/- 0…9,999,999

Net gigaVAR hours

12

30725-26

kVARh Net

+/- 0.000…999,999

Net kiloVAR hours

13

30727-28

GVAh Net

0…9,999,999

Net gigaVA hours

14

30729-30

kVAh Net

0.000…999,999

Net kiloVA hours

15

30731-32

kWatt Demand

+/- 0.000…9,999,999

The average real power during
the last demand period.

16

30733-34

kVAR Demand

+/- 0.000…9,999,999

The average reactive power
during the last demand period.

Advertising