Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 82

Advertising
background image

82

Publication 1408-UM001B-EN-P - May 2008

Appendix A Powermonitor 1000 Data Tables

18

30919

Ethernet Communications

0…511

0 indicates normal operation.
Bit 0 = Ethernet Communications status
Bit 1 = SNTP Server timeout status
Bit 2 = Duplicate IP Address status
Bit 3 = Invalid IP/Netmask address
Bit 4 = Invalid gateway address
Bit 5 = Invalid SNTP time server address
Bit 6 = Modbus stack run status
Bit 7 = Demand broadcast thread run status
Bit 8 = SNTP thread run status

19

30920

Input Over Range

0…3

0 indicates normal operation.
Bit 0 = Voltage Input over range
Bit 1 = Current Input over range

20

30921

Phase Loss Detection

0…7

0 Indicates normal running condition.
Bit 0 = Loss of phase A
Bit 1 = Loss of phase B
Bit 2 = Loss of phase C

21

30922

Configuration Locked

0…1

Reports 1 if configuration lock is applied.

22

30923

Password Accepted

0…1

1 indicates the password is verified and active

23

30924

Error Recorded

0

Is incremented by 1 when an internal error
happens

24

30925

Troubleshooting Times
Remaining

0…30

Remaining times for troubleshooting mode.

Unit Run Status Results

Element
No.

Modbus
Address

Element Name

Range

Description