Appendix A Powermonitor 1000 Data Tables

Log Configuration Parameters

CSP File No.

N15

CIP Instance

8

No. of Elements

12

No. of Words

12

Data Type

Integer

Data Access

Read/Write

Log Configuration

Element
No.

Modbus
Address

Element Name Default

Value

Range

TR

1

TR

2

EM

1

EM

2

EM

3

Description

0

40501

Password

0

0…
9999

When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.

1

40502

Energy Log
Interval

15 min

-1…60

Selects how often a record is logged
(minutes). A value of 0 disables periodic
logging of records. A value of –1 causes
logging of records to be synchronized to
the end of the demand interval.

2

40503

Energy Log
Mode

1

0…1

This parameter set the action of the log
once is has filled to capacity. Setting the
option to 0 allows the log to fill but stops
at the end. Option 1 lets the log fill and
then oldest records are deleted and
replaced with new records.

0 = Fill and Stop
1 = Overwrite, When the log is filled new
records replace the oldest records.

3

40504

Time of Use Log
Auto Log
Setting

31

0…31

Automatically stores the current record
for the month replacing the oldest record
if the log is full. The log holds 12 months
plus the current record.

0 = Disables the auto clear feature.
1 = Store and clear the table on the 1st
day of each month.
2 = 2nd Day
3 = 3rd day

29…31 = Store and clear table at the
last day of the month.