Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 68

Advertising
background image

68

Publication 1408-UM001B-EN-P - May 2008

Appendix A Powermonitor 1000 Data Tables

Wiring Diagnostics Results Parameters

CSP File No.

F20

CIP Instance

13

No. of Elements

21

No. of Words

42

Data Type

Float

Data Access

Read

Wiring Diagnostics Results

Element
No.

Modbus
Address

Element Name

Units

Range

TR1

TR2

EM1

EM2

EM3

Description

0

30101-2

Wiring Status

0…5

This is the overall status of the
wiring diagnostic test.
0 = Pass
1 = Failed
2 = Input Level Low
3 = Disabled
4 = Waiting Command
5 = Out of range

1

30103-4

Voltage Input
Missing

-1…123

Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing

2

30105-6

Voltage Input
Inverted

-1…123

Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted

Advertising