Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 51

Advertising
background image

Publication 1408-UM001B-EN-P - May 2008

51

Powermonitor 1000 Data Tables Appendix A

Serial RS-485 Port Configuration Parameters

CSP File No.

N12

CIP Instance

5

Applies to

All models

No. of Elements

9

No. of Words

9

Data Type

Integer

Data Access

Read/Write

Serial RS-485 Port Configuration

Element
No.

Modbus
Address

Element Name

Default
Value

Range

Description

0

40201

Password

0

0…9999

When writing the complete table this parameter allows the input
data to be accepted. When writing a single parameter the separate
password table should be used. Returns -1 on a read.

1

40202

Protocol Setting

1

0…3

The protocol selection for communications.

0 = DF1 Half Duplex Slave
1 = DF1 Full Duplex
2 = Modbus RTU Slave
3 = Auto Sense
4 = DH485

2

40203

Serial Delay

2
(10 ms)

1…15

The setting times 5 = milliseconds that the unit waits before
responding to a communication request. Useful for consistent
communications and slow devices.

3

40204

Baud Rate

5

0…6

The serial communications baud rate.

0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38,400
6 = 57,600

4

40205

DF1, DH485,
Modbus Address

Device
ID,
31 for
DH485

1…247
(DF1,
Modbus)
0…31
(DH485)

During production the Device ID is printed on the nameplate. This ID
then becomes the default address for DF1 and Modbus.