Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 52

Advertising
background image

52

Publication 1408-UM001B-EN-P - May 2008

Appendix A Powermonitor 1000 Data Tables

5

40206

Data Format

0

0…2
(2 for
DH485)

Parity, number of data bits, number of stop bits

0 = No parity, 8 data bits, 1 stop bit
1 = Odd parity, 8 data bits, 1 stop bit
2 = Even parity, 8 data bits, 1 stop bit

6

40207

Inter Character
Timeout

0

0…
6553

Specifies the minimum delay between characters that indicates the
end of a message packet for Modbus protocol. 0 = 3.5 character
times in default. The unit is ms.

8

40208

Maximum Node
Address

3

1…31

Specifies the maximum node address on a DH485 network.

9

40209

Reserved

0

0

Reserved for future use.

Serial RS-485 Port Configuration

Element
No.

Modbus
Address

Element Name

Default
Value

Range

Description

Ethernet Configuration Parameters

CSP File No.

N13

CIP Instance

6

No. of Elements

23

No. of Words

23

Data Type

Integer

Data Access

Read/Write

Ethernet Configuration

Element
No.

Modbus
Address

Element Name

Default
Value

Range

TR1

TR2

EM1

EM2

EM3

Description

0

40301

Password

0

0…9999

• •

• • •

When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.

1

40302

IP Address Byte a
(aaa.xxx.xxx.xxx)

192

0…255

• •

• • •

The 1st Octet of the Static IP Address.

2

40303

IP Address Byte b
(xxx.bbb.xxx.xxx)

168

0…255

• •

• • •

The 2nd Octet of the Static IP Address.

3

40304

IP Address Byte c
(xxx.xxx.ccc.xxx)

254

0…255

• •

• • •

The 3rd Octet of the Static IP Address.

4

40305

IP Address Byte d
(xxx.xxx.ddd.xxx)

Unit ID

0…255

• •

• • •

The 4th Octet of the Static IP Address.