Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 64

Advertising
background image

64

Publication 1408-UM001B-EN-P - May 2008

Appendix A Powermonitor 1000 Data Tables

Log Request Table Parameters

CSP File No.

N17

CIP Instance

10

No. of Elements

11

No. of Words

11

Data Type

Integer

Data Access

Read/Write

Log Request Table

Element
No.

Modbus
Address

Element Name Default

Value

Range

TR1

TR2

EM1

EM2

EM3

Description

0

40701

Selected Log

0

0…5

Selects the log that information is
returned from. Once a single request
has been made the auto return feature
will bring back successive records
each time the log is read. Some logs
support individual record requests.
1 = Unit Status Log
2 = Min/Max Log
3 = Energy Log
4 = Load Factor Log
5 = Time of Use Log kWh
6 = Time of Use Log kVAR
7 = Time of Use Log kVA
If your catalog number does not
support the requested log item the
power monitor will ignore the request.

1

40702

Chronology of
Auto Return
Data

1

0…1

The date chronology of the returned
records.
0 = Reverse direction
1 = Forward direction

2

40703

The Min/Max
record to be
returned

0

0…35
0…31
0…15

Selects the Min/Max record number
to be returned. See the table for
Min/Max record list.
0 = Use incremental return and the
chronology selected.
EM3 = 1…35
TR2 = 1…31
TR1 = 1…15

3

40704

Number of Unit
Status Records

-

1…50

On a read of this table the value of this
parameter is the number of Unit
Status Records available. This log is
only returned using the incremental
return method.