Appendix A Powermonitor 1000 Data Tables

Analog Input Configuration Parameters

CSP File No.

F10

CIP Instance

3

Applies to

All models

No. of Elements

7

No. of Words

14

Data Type

Float

Data Access

Read/Write

Analog Input Configuration

Element
No.

Modbus
Address

Element Name

Default
Value

Range

Description

0

40001-2

Password

0

0…9999

When writing the complete table this parameter allows the
input data to be accepted. When writing a single parameter
the separate password table should be used. Returns -1 on a
read.

1

40003-4

Voltage Mode

2

0…4

Should match the external electrical system and how it is
wired to the Powermonitor’s voltage and current input
terminals. Refer to the installation manual wiring diagrams.

0 = Direct Delta
1 = Open Delta
2 = Wye
3 = Single Phase
4 = Demo

2

40005-6

PT Primary

480

1.00…
50,000

The first value of the PT ratio (xxx:xxx) indicating the nominal
voltage present at the high-end of the transformer. If no
transformer is used (for direct connect of up to 347V L-N or
600V L-L), set the PT ratio to any valid 1:1 ratio (for example
480:480).

3

40007-8

PT Secondary

480

1.00…
600.00

The second value of the PT ratio (xxx:xxx) indicating the
nominal voltage present at the low-end of the transformer.

4

40009-10

CT Primary

5

5.00…
50,000

The first value of the CT ratio (xxx:5) indicating the nominal
current present at the high-end (primary side) of the
transformer.

Example: PRI = 1000. Setting = 1000:5.

5 A is the nominal secondary current of the CT.

5

40011-12

System PF Setting

2

0…2

0 = Leading -97…89
1 = High -85…98
2 = Low -52…-95

6

40013-14

Reserved

0

0

Reserved for future use.