Rslinx classic software opc server setup, Rslinx software opc server setup, Setup opc topic – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 35

Advertising
background image

Publication 1408-UM001B-EN-P - May 2008

35

SCADA Applications Chapter 5

Configure EtherNet/IP Network Using Ethernet Devices Driver

1. Create an Ethernet devices driver in RSLinx software.

2. Add the IP address of the power monitor to the driver station

mapping.

3. Perform an RSWho to verify that RSLinx software is

communicating to the power monitor.

RSLinx software driver configuration is complete.

Configure EtherNet/IP Network Using Ethernet/IP Driver

1. Create an Ethernet/IP driver in RSLinx software.

2. Make selections to browse the local or remote subnet as

appropriate.

3. Perform an RSWho to verify that RSLinx software is

communicating to the power monitor.

RSLinx software driver configuration is complete.

RSLinx Classic Software
OPC Server Setup

You can setup RSLinx software as an OPC Server to serve data from a
power monitor to an OPC 2.0 compliant application. You must first
setup an RSLinx driver to communicate to the power monitor. You can
then create an OPC topic to serve data to your SCADA application.

Setup OPC Topic

Follow these steps to setup a DDE/OPC topic in RSLinx software for
the power monitor.

1. Open RSLinx software.

IMPORTANT

The power monitor makes a connection to either the RSLinx
Ethernet Devices driver or the Ethernet/IP driver on a single
computer but not both simultaneously.

Advertising
This manual is related to the following products: