Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 73

Advertising
background image

Publication 1408-UM001B-EN-P - May 2008

73

Powermonitor 1000 Data Tables Appendix A

4

30409-10

GWh Fwd

0…9,999,999

Forward gigawatt hours

5

30411-12

kWatth Fwd

0.000…999,999

Forward kilowatt hours

6

30413-14

GWh Rev.

0…9,999,999

Reverse gigawatt hours

7

30415-16

kWatth Rev.

0.000…999.999

Reverse kilowatt hours

8

30417-18

GWh Net

+/- 0…9,999,999

Net gigawatt hours

9

30419-20

kWatth Net

+/- 0.000…999,999

Net kilowatt hours

10

30421-22

GVARH Fwd

0…9,999,999

Forward gigaVAR hours

11

30423-24

kVARh Fwd

0.000…999,999

Forward kiloVAR hours

12

30425-26

GVARH Rev.

0…9,999,999

Reverse gigaVAR hours

13

30427-28

kVARh Rev.

0.000…999,999

Reverse kiloVAR hours

14

30429-30

GVARH Net

+/- 0…9,999,999

Net gigaVAR hours

15

30431-32

kVARh Net

+/- 0.000…999,999

Net kiloVAR hours

16

30433-34

GVAh Net

0…9,999,999

Net gigaVA hours

17

30435-36

kVAh 0.000…999,999

Net kiloVA hours

18

30437-38

Metering Iteration

0…9,999,999

Increments by 1 for each new
metering calculation.

Energy Results

Element
No.

Modbus
Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

Demand Results Parameters

CSP File No.

F24

CIP Instance

17

No. of Elements

9

No. of Words

18

Data Type

Float

Data Access

Read

Demand Results

Element
No.

Modbus
Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

0

30501-2

kWatt Demand

+/- 0.000…9,999,999

The average real power during the
last demand period.

1

30503-4

kVAR Demand

+/- 0.000…9,999,999

The average reactive power during
the last demand period.

2

30505-6

kVA Demand

0.000…9,999,999

The average apparent power during
the last demand period.

Advertising