25
Configure the Adapter with RSLogix5000 software Chapter 3
To configure your adapter using the BootP utility, perform the following steps:
1. Run the BootP software.
In the BOOTP Request History panel you see the hardware addresses of
devices issuing BootP requests.
2. Double-click the hardware address of the device you want to configure.