Rockwell Automation Publication 1734-UM017B-EN-P - October 2013

53

Chapter

5

Configure the Adapter for Direct Connection
and Rack Optimization in RSLogix 5000
Software

Overview

This chapter guides you through the steps required to configure your AENTR
adapter with both direct and rack-optimized I/O connections using
RSLogix 5000 software.

You can mix I/O connection formats for different I/O modules communicating
through the same adapter. I/O modules set up to use rack optimization
communicate at the rate of the RPI configured for the adapter.

I/O modules controlled by a direct I/O connection communicate at their own set
RPI. The RPI of the rack-optimized I/O connection has no bearing on the direct
I/O connections. The modules presented in this chapter have a configuration
using RSLogix 5000 software, revision 11. The chapter contains the following
main sections

.

Topic

Page

Set Up the Hardware

54

Create the Example Application

55

Configure the I/O Modules

56

Add the Local EtherNet/IP Bridge to the I/O Configuration

56

Add the POINT I/O Adapter to the I/O Configuration

60

Add the POINT I/O Modules and Configure for Rack-optimized Connection

64

Add the POINT I/O Module and Configure For Direct Connection

66

Download the Program to the Controller

70

Verify the Module Chassis Size

71

Access Module Data

74

ATTENTION: You must only use Series C and above POINT I/O modules
with 1734-AENTR EtherNet/IP Adapters. Series A or Series B POINT I/O
modules do not work with 1734-AENTR EtherNet/IP Adapters (does not
apply to POINTGuard modules).