Troubleshoot the Adapter Chapter 6
Network Status
Off
Device not initialized. Device does not have an IP address.
Flashing green
No CIP connections present. Device has an IP address, but no CIP connections are
established.
Solid green
CIP connections present. Device online and has an IP address, and CIP connections
are established.
Flashing red
One or more CIP connections in timed-out state. Check for I/O module failure
and controller operation.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Flashing red/green
Device is in self-test.
Link 1 or Link 2 Activity/Status Off
No link established.
Flashing green
Transmit or receive activity present at 100 Mbps.
Solid green
Link established at 100 Mbps
Flashing yellow
Transmit or receive activity present at 10 Mbps.
Solid yellow
Link established at 10 Mbps.
System Power
Off
Not active; adapter power is off, or DC-DC converter problem is present.
Solid green
System power is on; DC-DC converter output is active (5V).
Adapter Power
Off
Not active; adapter power is off
Solid green
Power is on; 24V input is present.
POINTBus Status
Off
Device is not online:
• Device has not completed Dup_MAC_ID test.
• Device not powered - check Adapter Status indicator.
Flashing green
Device is online but has no connections in the established state.
Firmware (NVS) update in progress.
Solid green
Device is online and has connections in the established state.
Flashing red
Recoverable fault occurred:
•At cycle power, the number of expected modules does not equal the number of
modules present.
•A module is missing.
•Node fault (I/O connection timeout) occurred.
Solid red
Unrecoverable fault has occurred:
• POINTBus is off.
Flashing red/green
LED cycle power test present.
Status Indicators for 1738-AENTR Adapter
Indicator
State
Description