Environmental specifications – Rockwell Automation 1738-AENTR, Series B POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP Adapters User Manual User Manual

Page 92

Advertising
background image

84

Rockwell Automation Publication 1734-UM017B-EN-P - October 2013

Appendix A Specifications

Environmental
Specifications

The 1734-AENTR and 1738-AENTR Dual Port EtherNet/IP Adapter modules
have the following environmental specifications.

Environmental Specifications

Attributes

1734-AENTR

1738-AENTR

Temperature,
operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry
Heat),
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock):
-20...55 °C (-4...131 °F)

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry
Heat),
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock):
-20...60 °C (-4...140 °F)

Temperature,
nonoperating

IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40...185 °F)

Temperature,
surrounding
air, max

55 °C (131 °F)

60 °C (140 °F)

Relative
humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 5 g @ 10...500 Hz

Shock,
operating

IEC60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Shock,
nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock): 50 g

Emissions

CISPR 11:
Group 1, Class A

CISPR 11:
Group 1, Class A

ESD immunity

IEC61000-4-2:
6 kV contact discharges
8 kV air discharges

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF
immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B
immunity

IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±3 kV @ 5 kHz on communications ports

IEC 61000-4-4:
±4 kV @ 2.5 kHz on power ports
±3 kV @ 5 kHz on communications ports

Surge
transient
immunity

IEC 61000-4-5:

• ±1 kV line-line (DM) and ±2 kV

line-earth (CM) on power ports

• ±2 kV line-earth (CM) on

communications ports

IEC 61000-4-5:

• ±1 kV line-line (DM) and ±2 kV

line-earth (CM) on power ports

• ±2 kV line-earth (CM) on

communications ports

Conducted RF
immunity

IEC61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz...80 MHz

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz...80 MHz

North
American
temp code

T4

-

IEC Temp
Code

T4

-