Environmental specifications – Rockwell Automation 1738-AENTR, Series B POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP Adapters User Manual User Manual
Page 92
84
Rockwell Automation Publication 1734-UM017B-EN-P - October 2013
Appendix A Specifications
Environmental
Specifications
The 1734-AENTR and 1738-AENTR Dual Port EtherNet/IP Adapter modules
have the following environmental specifications.
Environmental Specifications
Attributes
1734-AENTR
1738-AENTR
Temperature,
operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry
Heat),
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock):
-20...55 °C (-4...131 °F)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry
Heat),
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock):
-20...60 °C (-4...140 °F)
Temperature,
nonoperating
IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40...185 °F)
Temperature,
surrounding
air, max
55 °C (131 °F)
60 °C (140 °F)
Relative
humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5...95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating): 5 g @ 10...500 Hz
Shock,
operating
IEC60068-2-27 (Test Ea, Unpackaged Shock): 30 g
Shock,
nonoperating
IEC60068-2-27 (Test Ea, Unpackaged Shock): 50 g
Emissions
CISPR 11:
Group 1, Class A
CISPR 11:
Group 1, Class A
ESD immunity
IEC61000-4-2:
6 kV contact discharges
8 kV air discharges
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF
immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B
immunity
IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±3 kV @ 5 kHz on communications ports
IEC 61000-4-4:
±4 kV @ 2.5 kHz on power ports
±3 kV @ 5 kHz on communications ports
Surge
transient
immunity
IEC 61000-4-5:
• ±1 kV line-line (DM) and ±2 kV
line-earth (CM) on power ports
• ±2 kV line-earth (CM) on
communications ports
IEC 61000-4-5:
• ±1 kV line-line (DM) and ±2 kV
line-earth (CM) on power ports
• ±2 kV line-earth (CM) on
communications ports
Conducted RF
immunity
IEC61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz...80 MHz
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz...80 MHz
North
American
temp code
T4
-
IEC Temp
Code
T4
-