Chapter 6 Troubleshoot the Adapter

Status Indicators for ArmorPOINT I/O Adapters

The following describes the status indicators on the 1738-AENTR.

1738-AENTR
Series B

EtherNet I/P

Adapter
Status

Network
Activity

Network
Status

PointBus
Status

System
Power

Adapter
Power

conformance tested

PWR

IP ADDRESS

Link 2
Activity/
Status

Link 1
Activity/
Status

44830

Link 1 Activity/Status

Link 2 Activity/Status

Adapter Status
Network Activity
Network Status

System Power
Adapter Power

POINTBus Status

Status Indicators for 1738-AENTR Adapter

Indicator

State

Description

Adapter Status

Off

No power applied to device

Flashing green

Device needs commissioning due to missing, incomplete, or incorrect
configuration.

Solid green

Device operating normally

Flashing red

Recoverable fault:

• Complete firmware update
• Verify address switches.

Solid red

Unrecoverable fault:

• Self-test failure (checksum failure, RAM test failure at cycle power)
• Firmware fatal error).

Flashing red/green

Device is in self-test

Network Activity

Off

No link established with Port 1 or Port 2.

Flashing green

Transmit or receive activity present on Port 1 and/or Port 2 at 100 Mbps.
Transmit or receive activity present on Port 1 and/or Port 2.
One port at 100 Mbps and one port at 10 Mbps.

Solid green

Link established with Port 1 and/or Port 2 at 100 Mbps.
Link established with Port 1 and Port 2.
One port at 100 Mbps and one port at 10 Mbps

Flashing yellow

Transmit or receive activity present Port 1 and/or Port 2 at 10 Mbps.

Solid yellow

Link established with Port 1 and/or Port 2 at 10 Mbps.