40

Rockwell Automation Publication 1734-UM017B-EN-P - October 2013

Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software

Add the POINT I/O Modules to the I/O Configuration

You now add POINT I/O modules to the I/O Configuration List under the
adapter.

In this example, you add a 1734-OW2 relay output module and a 1734-OV4E
sink output module with standard configurations. Use these steps as a guide when
configuring different I/O modules for your system.

Add the Digital Relay Output Module

1. Highlight the 1734-AENTR/B adapter under the I/O Configuration

folder, right-click and select New Module.

The Select Module Type dialog displays.

2. Select the appropriate filter for Module Type Category (for the example we

selected Digital) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.

TIP

This example application uses I/O module default configurations.
For more information, refer to the POINT I/O Selection Guide,
publication

1734-SG001

.