Rockwell Automation 1738-AENTR, Series B POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP Adapters User Manual User Manual

Page 90

Advertising
background image

82

Rockwell Automation Publication 1734-UM017B-EN-P - October 2013

Appendix A Specifications

General Specifications

Attributes

1734-AENTR

1738-AENTR

Status indicators

3 red/green status indicators on CPU:

• Module Status
• Network Status (Ports 1 and 2

combined)

• POINTBus Status

1 green/yellow status indicator on
CPU:

• Network Activity (Ports 1 and 2)

2 green/yellow status indicators on
base:

• Link 1 Activity/Status
• Link 2 Activity/Status

2 green power supply status
indicators on DC-DC Converter:

• System Power (5V DC to

POINTBus Out)

• Field Power (24V DC from Field In)

3 red/green status indicators on CPU:

• Module Status
• Network Status (Ports 1 and 2

combined)

• POINTBus Status

1 green/yellow status indicator on
CPU:

• Network Activity (Ports 1 and 2)

2 green/yellow status indicators on
base:

• Link 1 Activity/Status
• Link 2 Activity/Status

2 green power supply status indicators
on DC-DC Converter:

• System Power (5V DC to POINTBus

Out)

• Adapter Power (24V DC from Field

In)

Wire Size

Power connections: 0.34... 2.1 mm

2

(22...14 AWG) solid or stranded copper

wire rated @ 75 °C (167 °F ) or greater, 1.2 mm (3/64 in.) insulation max or
90

°C (194 °F ) for ControlLogix.

Ethernet wiring: RJ45 connector according to IEC 60603-7, 2 or 4 pair Category
5e min cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC
24702.

Power
consumption, max

10.4 W @ 28.8V DC

Wiring category

(1)

1 – on communications ports

1 – on power ports

Power dissipation,
max

6.3 W @ 28.8V DC

Input overvoltage
protection

Reverse polarity protected

Thermal
dissipation, max

21.5 BTU/hr @ 28.8V DC

Isolation voltage

50V (continuous), Reinforced
Insulation Type, between all circuits.
Type tested @ 500V AC for 60 s

50V (continuous), Basic Insulation
Type. Type Tested @ 500V AC for 60 s:

• Comm to system
• Comm to user power
• User power to system
• User power to ground
• System to ground

Field power supply 10...28.8V DC @ 10A

10...28.8V DC @ 10A

Field power output 10...28.8V DC @ 9A

10...28.8V DC @ 9A

Module input

10...28V DC @ 1000 mA

10...28V DC @ 1000 mA

Dimensions
(HxWxD), approx.

76.2 x 73.0 x 133.4 mm
(3.0 x 2.87 x 5.25 in.)

112 x 123 x 67 mm
(4.41 x 4.84 x 2.64 in.)

Mounting type

-

Metal panel

Enclosure type
rating

None (open-style)

Meets IP65/66/67/69K (when marked)

Terminal base
screw torque

0.8 Nm (7 lb-in)

0.8 Nm (7 lb-in)

Weight, approx.

0.28 Kg (0.62 lb)

0.33 Kg (0.72 lb)

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring

and Grounding Guidelines, publication

1770-IN041

and to the appropriate System Level Installation Manual.